Multiplus-II 48/3000/35-32 Gx
VICTRON 230V MULTIPLUS PURE SINE WAVE INVERTER / CHARGER • 48V 3000VA INVERTER 35A BATTERY CHARGER WITH 32A AUTOMATIC TRANSFER SWITCH
Brand: Victron
Reference No. PMP482306000
Victron Multiplus-II GX:
An Inverter/Charger with device networking built-in, the MultiPlus-II GX communicates with a solar charger, batteries, and other devices to control a grid-connected, off-grid, or remote power installation. Capable of parallel operation for increased power output, or battery charge-rates, the MultiPlus-II GX can also be configured for three-phase supply. A host of advanced features - such as uninterrupted power supply, setting load limits, and supplementing limited grid-power availability with battery power - can all be controlled straight from your phone or smart device. Remote monitoring is also possible.
Features:
A MultiPlus-II with LCD and GX functionality- The MultiPlus-II GX integrates a MultiPlus-II inverter/charger and a GX device with a 2 x 16 character display.
Display and Wi-Fi- The display reads battery, inverter and solar charge controller parameters. The same parameters can be accessed with a smartphone or other Wi-Fi enabled device.
GX device-
The integrated GX device includes:
A VE.Can interface. This can be used to connect to Victron VE.Can devices (eg VE.Can MPPTs), or the port can be reconfigured via the Remote Console for use with a compatible CAN-bus Li-ion Battery.
A USB port.
A Ethernet port.
A VE.Direct port.
Applications- The MultiPlus-II GX is intended for applications where additional interfacing with other products and/or remote monitoring is required, such as on-grid or off-grid energy storage systems and certain mobile applications.
Parallel and three phase operation- Only one GX unit is needed in case of Parallel and three phase operation.
MultiPlus-II GX | 48/3000/35-32 |
INVERTER/CHARGER | |
PowerControl & PowerAssist | Yes |
Transfer switch | 32A |
Maximum AC input current | 32A |
Auxiliary output | Yes (32A) |
INVERTER | |
Input voltage range | 38 – 66V |
Output | Output voltage: 230 VAC ± 2% Frequency: 50 Hz ± 0,1% (1) |
Cont. output power at 25°C (3) | 3000VA / 2400W |
Cont. output power at 40°C / 65°C | 2200W / 1700W |
Maximum apparent feed-in power | 2500VA |
Peak power | 5500W |
Maximum efficiency | 95% |
Zero load power | 11W |
Zero load power in AES mode | 7 W |
Zero load power in Search mode | 2W |
CHARGER | |
AC Input | Input voltage range: 187-265 VAC Input frequency: 45 – 65 Hz |
Charge voltage 'absorption' | 57,6V |
Charge voltage 'float' | 55,2V |
Storage mode | 52,8V |
Maximum battery charge current (4) | 35A |
Battery temperature sensor | Yes |
Programmable relay (5) | Yes |
Protection (2) | a - g |
VE.Bus communication port | For parallel and three phase operation, remote monitoring and system integration |
General purpose com. port | Yes, 2x |
GENERAL | |
Interfaces | VE.Can, USB, Ethernet, VE.Direct, Wi-Fi |
Remote on-off | Yes |
Operating temp. range | -40 to +65°C (fan assisted cooling) |
Humidity (non-condensing): | max 95% |
ENCLOSURE | |
Material & Colour | Steel, blue RAL 5012 |
Protection category | IP21 |
Battery-connection | M8 bolts |
230 V AC-connection | Screw terminals 13 mm2 (6 AWG) |
Weight | 19kg |
Dimensions (hxwxd) | 506 x 275 x 147 mm |
STANDARDS | |
Safety EN-IEC 60335-1, EN-IEC60335-2-29 EN-IEC 62109-1, EN-IEC 62109-2 | |
Emission / Immunity Anti-islanding | EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 |
1) Can be adjusted to 60Hz 2) Protectionkey: a) output short circuit b) overload c) batteryvoltagetoohigh d) batteryvoltagetoolow e) temperature toohigh f)230 VAC on inverteroutput g) input voltage ripple toohigh | 3) Non-linear load, crest factor3:1 4) At 25°Cambient 5) Programmablerelaywhichcanbesetforgeneralalarm, DCundervoltageorgensetstart/stopfunction. AC rating: 230V / 4A, DC rating: 4A up to 35VDC and 1A up to 60VDC |